Commissioning
2.6 First commissioning control mode vector U/f in booksize format
What to do?
5
Drive setting
5.1
Configuring the
motor
5.2
Configuring the
motor data
5.3
Configuring a
motor holding
brake
Caution
If the motor is replaced after transferring project data from the programming device to the drive, then before any data is
transferred again, the pulse frequency must be checked.
112
You can select the motor standard (IEC/NEMA) and power unit
application (duty cycles).
1. Enter a name for the motor (e.g. equipment code).
2. If your motor has its own DRIVE-CLiQ interface, select the
item.
3. Click on "Continue >".
When commissioning, the motor data is automatically transferred
to the Control Unit.
1. If you use a standard motor select the item, "Select standard
motor from list".
2. Select the standard motor type from the "Motor type" list.
3. Then, select your motor.
4. Click on "Continue >".
1. If your motor is not in the default list, select Enter motor data
and jump to point 5.2.
2. Click on your motor type in the "Motor type" list.
3. Click on "Continue >".
1. Enter your motor data according to the data sheet.
1. Alternatively, after entering the motor data, carry out a motor
identification when commissioning for the first time.
Alternatively, you can use motor data from the template.
1. Follow the wizard by clicking on "Next >".
2. If known, you can enter the mechanical data of the motor and
the drive train or the data of a PE spindle.
3. If necessary, select a complete calculation of the
motor/controller data without equivalent circuit diagram data.
4. For this example, select the simple drive.
1. If you are not using a motor holding brake, click on "Continue
>".
2. If you are using a motor holding brake, you can select and
configure the brake in this window.
3. Click on "Continue >".
How to do it?
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Comment
-
You can select a standard
motor from the list of
motors or manually enter
the motor data. You can
then select the motor type.
If you have no mechanical
data to enter, then the data
are estimated based on the
rating plate data. The
equivalent circuit diagram
data is also estimated on
the basis of the data on the
rating plate or determined
by means of automatic
motor data identification.
For further information see
Function Manual.
Commissioning Manual