Preparation for commissioning

1.3 PROFIBUS components

1.3
PROFIBUS components
For communication via PROFIBUS, the following components are necessary.
● A communication module for programming device/PC connection via the PROFIBUS
● PROFIBUS connection to a programming device/PC via USB port (USB V2.0), e.g. with
Connecting cable
Connecting cable between PROFIBUS adapter and programming device/PC, such as
● CP 5xxx cable, Order No.: 6ES7901-4BD00-0XA0
● MPI cable (SIMATIC S7), Order No.: 6ES7901-0BF00-0AA0
Cable lengths
Table 1- 4
9.6 k to 187.5 k
500 k
1.5 M
3 to 12 M
20
interface:
the PROFIBUS adapter CP5711.
Structure: USB port (USB V2.0) + adapter with 9-pin SUB-D socket connector to connect
to PROFIBUS.
Used with driver SIMATIC Net PC Software Edition 2008 + SP2
Order No.: 6GK1571-1AA00
Permissible PROFIBUS cable lengths
Baud rate [bit/s]
Max. cable length [m]
1000
400
200
100
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2