Additional Modules; Control Supply Module; Sensor Module Cabinet Smc10 / Smc20 - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

3.1.3

Additional modules

3.1.3.1

Control Supply Module

Table 3- 33
Control Supply Module – description of the LEDs
LED
Color
READY
-
off
Green
Continuous
DC LINK
-
off
Orange
Continuous
Red
Continuous
3.1.3.2

Sensor Module Cabinet SMC10 / SMC20

Table 3- 34
Sensor Module Cabinet 10/20 (SMC10/SMC20) – description of the LEDs
LED
Color
RDY
-
off
READY
Green
Continuous
light
Orange
Continuous
light
Red
Continuous
light
Green/
0.5 Hz
red
flashing
light
2 Hz
flashing
light
Green/
Flashing
orange
light
or
Red/
orange
Commissioning Manual
Commissioning Manual, (IH1), 01/2012, 6SL3097-4AF00-0BP2
Status
Electronics power supply is missing or outside permissible
tolerance range.
Component is ready to operate.
Electronics power supply is missing or outside permissible
tolerance range.
DC link voltage within permissible tolerance range.
DC link voltage outside permissible tolerance range.
State
Electronic power supply is missing or outside permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
DRIVE-CLiQ communication is being established.
This component has at least one fault.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON
Component recognition via LED is activated (p0144)
Note:
Both options depend on the LED status when component
recognition is activated via p0144 = 1.
Description, cause
Description, cause
Diagnostics
3.1 Diagnostics via LEDs
Remedy
Remedy
Remedy and
acknowledge fault
Carry out a POWER
ON
207