Diagnostics
3.1 Diagnostics via LEDs
3.1.3

Additional modules

3.1.3.1

Control Supply Module

Table 3- 33
Control Supply Module – description of the LEDs
LED
Color
READY
Green
DC LINK
Orange
Red
3.1.3.2

Sensor Module Cabinet SMC10 / SMC20

Table 3- 34
Sensor Module Cabinet 10/20 (SMC10/SMC20) – description of the LEDs
LED
Color
RDY
READY
Green
Orange
Red
Green/red
Green/
orange
or
Red/orange
262
State
Description, cause
off
Electronic power supply is missing or outside permissible
tolerance range.
Continuous
Component is ready to operate.
light
off
Electronic power supply is missing or outside permissible
tolerance range.
Continuous
DC link voltage within permissible tolerance range.
light
Continuous
DC link voltage outside permissible tolerance range.
light
State
Description, cause
off
Electronic power supply is missing or outside permissible
tolerance range.
Continuous
The component is ready for operation and cyclic DRIVE-
light
CLiQ communication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
light
Continuous
At least one fault is present in this component.
light
Note:
LED is controlled irrespective of the corresponding messages
being reconfigured.
Flashing light
Firmware is being downloaded.
0.5 Hz
Flashing light
Firmware download is complete. Wait for POWER ON
2 Hz
Flashing light
Component recognition via LED is activated (p0144).
Note:
Both options depend on the LED status when module
recognition is activated via p0144 = 1.
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Remedy
Remedy
Remedy and
acknowledge fault
Carry out a
POWER ON