Commissioning
2.2 STARTER commissioning tool
10. Then click on the "Assign Name" button.
11. Click on the "Update" button.
12. Close the "Edit Ethernet node" window.
13. Activate the option button in front of the detected drive unit and click the "Accept" button.
14. Click on the button "Connect to target system" and then call the menu "Target system >
80
– The data transfer is confirmed.
– The bus node is detected as drive unit and is consecutively numbered.
– The address, device name and the type are specified.
The SINAMICS drive with CBE20 is transferred as a drive object into the project tree. You
can now continue to configure the drive object.
Load > To target device", to load the project to the Control Unit memory card.
The IP address and device name for the Control Unit are stored on the memory card
(non-volatile).
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Commissioning Manual