Commissioning
2.13 Commissioning SIMOTICS 1FW6 built-in torque motors
The assignment of connector interface X200 can be found in the "SINAMICS S120 Manual
Control Units and Additional System Components".
Terminal Module TM120
Terminal Module TM120 is a DRIVE-CLiQ component for temperature evaluation with safe
isolation, see also "SINAMICS S120 Manual for Control Units and Additional System
Components" in the Chapter "Supplementary system components".
TM120 is an autonomous input/output component. You can freely assign the temperature
channels to any Motor Module.
You can assign every channel to the following sensor types:
● PTC
● KTY 84
● Bimetallic NC contact
Note
Standard topology
The standard topology is:
Motor Module - Terminal Module TM120 - Sensor Module Cabinet SMC20
Parameterization
For a standard configuration with correct pre-assignment of the temperature channels, the
Terminal Module TM120 must be located between the Sensor Module SMC20 and the Motor
Module (DRIVE-CLiQ port X202).
If this is not the case, you must parameterize all of the required temperature channels in both
the Motor Module and Terminal Module TM120.
You must always carefully check the temperature shutdown circuits (e.g. by disconnecting
the sensors) before commissioning the motor for the first time.
Use the expert list to parameterize the drive.
190
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3