Basic Line Module Booksize - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Diagnostics
3.1 Diagnostics via LEDs
3.1.2.2

Basic Line Module booksize

Table 3- 16
Meaning of the LEDs on the Basic Line Module
State
Ready
DC link
Off
Off
Green
Off
Orange
Red
Orange
Orange
Red
Green / red
flashing light
0.5 Hz
Green / red
flashing light
2 Hz
Green /
orange
or
Red / orange
flashing light
Risk of electric shock as a result of the high DC link voltage
Hazardous DC link voltages may be present at any time regardless of the state of the "DC
link" LED.
Note the warning information on the component!
250
Description, cause
Electronic power supply is missing or outside permissible
tolerance range.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is present.
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is too high.
DRIVE-CLiQ communication is being established.
At least one fault is present in this component.
Note:
LED is controlled irrespective of the corresponding messages
being reconfigured.
Firmware is being downloaded.
Firmware download is complete. Wait for POWER ON.
Component detection via LED is activated (p0124).
Note:
Both options depend on the LED status when module
recognition is activated via p0124 = 1.
WARNING
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Remedy
Check the line voltage.
Remedy and acknowledge
fault.
Carry out a POWER ON
Commissioning Manual

Advertisement

Table of Contents
loading

Table of Contents