Terminal Module Tm150; Terminal Module Tm41 - Siemens SINAMICS S120 Commissioning Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Diagnostics
3.1 Diagnostics via LEDs
3.1.4.4

Terminal Module TM150

Table 3- 46
Meaning of the LEDs at the Terminal Module TM150
LED
Color
Green
Orange
READY
Red
Green/
Red
Green/
orange
or
red/
orange
3.1.4.5

Terminal Module TM41

Table 3- 47
Meaning of the LEDs on the Terminal Module TM41
LED
Color
READY
-
Green
Orange
Red
Green/red
Green/
orange
or
Red/
orange
270
State
Description, cause
Off
Electronic power supply is missing or outside
permissible tolerance range.
Continuous light The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
Continuous light DRIVE-CLiQ communication is being established.
This component has at least one fault.
Continuous light
Note:
LED is controlled irrespective of the corresponding
messages being reconfigured.
Flashing light
Firmware is being downloaded.
0.5 Hz
Flashing light
Firmware has been downloaded.
2 Hz
Wait for POWER ON.
Component recognition via LED is activated (p0154).
Flashing light
Note:
2 Hz
Both options depend on the LED status when module
recognition is activated via p0154 = 1.
Status
Off
Electronics power supply is missing or outside the
permissible tolerance range.
Continuous
The component is ready for operation and cyclic
light
DRIVE-CLiQ communication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
light
Continuous
At least one fault is present in this component.
light
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
0.5 Hz flashing
Firmware is being downloaded.
light
2 Hz flashing
Firmware download is complete. Wait for POWER ON. Carry out a POWER
light
Flashing light
Component recognition via LED is activated (p0154).
Note:
Both options depend on the LED status when
component recognition is activated via p0154 = 1.
Description, cause
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Remedy
Check power supply
Remedy and
acknowledge fault
Carry out a POWER
ON
Remedy
Remedy and
acknowledge fault
ON