Commissioning
2.2 STARTER commissioning tool
5. Click on "Close".
6. Call the menu "Tools > Set PG/PC interface ..." and click on the "Properties" button.
7. Activate or deactivate the option "PG/PC is the only master on the bus".
Note
PROFIBUS setting
• Baud rate
• PROFIBUS addresses:
2.2.4

Activating online operation: STARTER via Ethernet

The Control Unit can be commissioned with the programming device (PG/PC) via the
integrated Ethernet Interface. This interface is provided for commissioning purposes only
and cannot be used to control the drive in operation. Routing with a possibly inserted CBE20
expansion card is not possible.
Precondition
● STARTER from version 4.1.5 or higher
● Control Unit CU320-2 DP from version "C" and higher or CU320-2 PN
STARTER via Ethernet (example)
Figure 2-5
68
– Connect STARTER to an operational PROFIBUS:
The STARTER commissioning tool automatically detects the baud rate used by
SINAMICS for PROFIBUS, and this is then used.
– Connect STARTER for commissioning:
The Control Unit automatically detects the baud rate set in the STARTER
commissioning tool, and this is then used.
The PROFIBUS addresses for the individual drive units must be specified in the project
and must match the address settings on the devices.
Connecting the programming device to the target device via Ethernet (example)
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3