Diagnostics
3.1 Diagnostics via LEDs
3.1.1.2

Description of the LED states of a CU310-2

There are four LEDs on the front panel of the CU310-2 DP housing.
Table 3- 8
RDY
COM
OUT > 5V
MOD
The various LEDs are switched on and off as the control unit is powered up (depending on
the phase the system is currently running through). When switched on, the color of the LEDs
shows the status of the corresponding power-up phase.
In the event of a fault, power up will be ended in the corresponding phase. The LEDs that
are switched on retain their colors so that the fault can be determined on the basis of the
combination of the color LEDs that are lit and unlit.
All the LEDs go out briefly if the CU310-2 DP has powered up without error. The system is
ready for operation when the LED "RDY" is permanently green.
All the LEDs are controlled by the software loaded during operation.
Control Unit 310-2 DP while powering up
Table 3- 9
Load software
RDY
COM
Orange
Orange
Red
Red
Red
Red
Red
Red
Flashing light 2
Hz
Red
Red
Flashing light 2
Flashing light 2
Hz
Hz
244
LEDs
Ready
Option Board
Encoder current supply > 5 V (TTL/HTL)
Operating mode (reserved)
LED
OUT > 5V
Orange
Orange
Off
Off
Off
Off
State
MOD
POWER ON
Off
Hardware
reset
Off
BIOS loaded
Off
BIOS error
Off
File error
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3
Comment
All LEDs light up for approx. 1 s
After pressing the RESET button the
LEDs light up for approx. 1 s
-
Error occurred while loading the
BIOS
Memory card not inserted or faulty
Software on memory card not
present or corrupted