Setup & Operation 8.2 Timing Specifications (I/O Remote Settings)

8.2 Timing Specifications

8.2.1 Design Notes for Remote Input Signals

The following charts indicate timing sequences for the primary operations of the
Controller.
The indicated time lapses (time durations) should be referred to only as reference value
since the actual timing values vary depending on the number of Manipulators and the
number of tasks running, as well as CPU speed of the Controller. Check carefully and
refer to the following charts for the timing interrelation when you enter an input signal.
During system design, make sure that you actuate only one remote input operation at a
time, otherwise an error will occur.
The pulse width of an input signal must be 25 or more milliseconds to be detected.

8.2.2 Timing Diagram for Operation Execution Sequence

CmdRunning
Output
Power High
Output
MotorOn
Output
AtHome
Output
MotorOn
Input
MotorOff
Input
Home
Input
PowerHigh
Input
PowerLow
Input
72
20
20
300
About 1000
Depending on
HOME motion
20
150
20
40
20
20
12
50
About 1000
[Unit: msec]