Fault Table (continued)
Fault
Fault Title
Controller
Number
Affected
15
Software
Primary
Error
16
Contactor
Primary
Fault
17
Throttle
Primary
Sensor
Fault
18
Traction
Primary
Bail Sensor
Fault
Greensmaster
®
eFlex 1021
20248SL Rev C
Fault Condition/Circuit
Description
The software has detected
an issue with reading the
throttle sensor.
The bus voltage was
high enough at power up
to require a discharge
before precharge. The bus
failed to discharge below
threshold in the required
amount of time.
At shutdown, the contactor
opens and the bus
discharges before shutting
the machine down. This
discharge failed to go
below the threshold in the
required amount of time.
The sensor signals are
outside the expected
range.
The sensor signals are
outside the expected
range.
Page 3–7
Additional
Service Actions
Notes
1.
Try rebooting machine,
disconnect and reconnect
the battery, look for short circuits
in the harness.
2.
Replace the TEC.
Most likely cause is a shorted
contactor.
Traction is
1.
Test the throttle sensor.
disabled.
2.
Test the throttle sensor circuit
wiring and connector P05.
3.
Replace throttle sensor.
Traction is
1.
Test the traction bail sensor.
disabled.
2.
Test the traction bail sensor
circuit wiring and connector
P26.
3.
Replace traction bail sensor.
Troubleshooting: Machine Faults