Siemens SiPass integrated Reference Manual page 22

Hide thumbs Also See for SiPass integrated:
Table of Contents

Advertisement

Operational Modes
5
22 | 66
Type
Mode
Input/Outpu
Passback
t
Passback No Message
Passback No Report –
Lock not activated
Passback Report – Lock
not activated
Input Disabled
Door Frame Auto Pre-
Alarm
Door Frame Dual Timer
Door Frame Held Only
Door Frame Manual Pre-
Alarm
Door Frame Sensor
Alarm/Normal
Description
The input is in alarm state until the passback
button has been pressed and the input delay is
activated. Triggering passback unlocks the door
latch.
The input is in alarm state until the passback
button has been pressed and the input delay is
activated. No passback message is reported
back to the system. The latch is not
automatically unlocked. Triggering passback
unlocks the door latch.
The input is in alarm state until the passback
button has been pressed and the input delay is
activated. No passback message is reported
back to the system. Triggering passback does
not unlock the door latch.
The input is in alarm state until the passback
button has been pressed and the input delay is
activated. Triggering passback does not unlock
the door latch.
Disables the input point.
A Pre-Alarm will sound before the main Door
Held Alarm. The Pre-Alarm will not be
registered on the Alarm Queue.
If the door is not returned to a normal state
within the Pre-Alarm time period, the Door Held
Alarm will sound and will be registered in the
alarm queue.
The Door Held Alarm will auto-matically stop
when the door returns to a normal state.
Defines the input point as a door contact sensor
that monitors the open or closed state of the
door. The input point will use both the Pre-
Alarm Delay and Input Delay times when
sending alarms.
In case when the door has a reader on the
outside but no reader (and no passback) on the
inside, this mode holds an open door virtually
for the Input Delay time duration set by the user
and prevents reporting the event as "door-
force".
A Pre-Alarm will sound before the main Door
Held Alarm. The Pre- Alarm will not be
registered on the Alarm Queue.
If the door is not returned to a normal state
within the Pre-Alarm time period, the Door Held
Alarm will sound and will be registered in the
alarm queue.
The Door Held will stop only when the door is
returned to a normal state and the alarm has
been acknowledged.
Defines the input point as a door contact sensor
that monitors the open or closed state of the
door.
Both changes to alarm and normal states are
reported to the system.
A6V11144326