Type
Command
Set state Alarm
Set state Normal
Unsecure (Disable)
Output
Allow Access
Cancel Permanent
Action
Fast Pulse
Return to Time
Schedule Control
Secure (Lock)
Single Pulse
Slow Pulse
Toggle Point
Unsecure (Unlock)
APB Area
Forgive All cards
(Anti-
Forgive Card
Passback
Area)
Override Mode
Reset Count
Restore Mode
Add Card
Remove Card
Intrusion
Arm
Clear Intrusion
Alarms
Disarm
Isolate Point
Description
Set the input to state Alarm. This is only applicable
for Sintony input points of type "Serial Comms
Input"
Set the input to state Normal. This is only
applicable for Sintony input points of type "Serial
Comms Input"
Disables the input, if it is currently enabled, until the
next change in Time Schedule.
Allows access at an output point. (Operates in the
same way as if a cardholder used their card to gain
valid access at the same point). The output point
will only be activated for the latch time.
Any current Permanent Command or Event Task,
or Access/Internal Action operating on the point will
be cancelled. The next Control State in the Control
State Queue will take effect.
The output point will activate in "fast pulse" mode.
The output will return to normal Time Schedule
control.
Locks the output (temporarily), if the output is
currently unlocked. The Duration can be set to :
- Until Time Schedule Change
- Permanent
Duration time can be specified in the HH:MM:SS
format.
The output will activate a single pulse.
The output will activate in "slow pulse" mode.
The state of the output will be toggled to the
reverse state.
Unlocks the output (temporarily), if the output is
currently locked, until the next change in Time
Schedule.
Forgives all cardholders currently in the area.
Forgives the specified cardholder.
Overrides the selected area with a specific mode.
Allows the count for an Anti-Passback area to be
reset to zero.
Restores the configured Anti-Passback mode.
Adds a card to an Anti-Passback area.
Removes a card from an Anti-Passback area.
Arms the selected intrusion area.
Clears all alarms in memory for the selected area or
specified room.
Disarms the selected intrusion area.
Manually isolates a point from an intrusion area,
excluding that point from a seal check when the
area is armed.