 Example 3 (Prohibited)
Capacity ratio
Model name
Outdoor unit
AJ072LELDH
Indoor unit 1 AUXK054GLEH
Indoor unit 2 AUXK054GLEH
Indoor unit 3 AUXK036GLEH
 Example 4 (OK)
Capacity ratio
Model name
Outdoor unit
AJ072LELDH
Indoor unit 1 AUXK054GLEH
1-1. Refrigerant system
Outdoor unit
Indoor unit 1
Indoor unit 2
Connectable
Cooling
Total
capacity
capacity
Min.
(kW)
22.4
22.4
14.0
(2) 50%
14.0
(1) 39.2
11.2
11.2
Outdoor unit
Connectable
Cooling
Total
capacity
capacity
Min.
(kW)
22.4
22.4
(2) 50%
14.0
(1) 14.0
11.2
- (06-3) -
Indoor unit 3
175%
indoor unit
capacity
Max.
(3) 150%
33.6
33.6 < 39.2 → Prohibited
Indoor unit 1
63%
indoor unit
capacity
Max.
(3) 150%
33.6
11.2 < 14.0 < 33.6 → OK
Judge
(3) < (1)
Judge
(2) ≤ (1) ≤ (3)