• Network converter for LonWorks
NOTE: Setting up more than one Network convertor in one VRF network system is prohib-
ited.
*: The sum total of the Touch panel controller, Central remote controller, Network converter for
Group remote controller, Modbus converter, and Network converter for LonWorks is a maxi-
mum of 16.
• Central remote controller address (Set N)
Before performing the initial setting, set the Central remote controller address first.
For details, refer to the setting manual.
1
*
: Setting up more than one Network converter in one VRF network system is prohibited.
2
*
: The sum total of the Touch panel controller, Central remote controller, Network converter
for Group remote controller, Modbus converter, and Network converter for LonWorks is a max-
imum of 16.
1-3. Manual address setting method
®
setting (Set M)
00
Central remote controller (Max. 16) *
- (07-15) -
15
Network converter
®
for L
W
*
ON
ORKS
01
02
03
1. System settings