¢ One way flow cassette type
Locally arranged pipe
Max. 300 mm
700 mm or less
Ceiling
700 mm
or less
• Use general hard polyvinyl chloride pipe (VP25) (O.D. 32 mm).
• Do not perform a rise, trap, and air bleeding.
• Provide a downward gradient (1/100 or more).
• Provide supporters when long pipes are installed.
• Use an insulation material as needed to prevent the pipes from freezing.
• Install the pipes in a way that allows for the removal of the control box.
5-2. Indoor unit
Gap of 1.5 to 2 m
Supporter
VP25
(O.D 32 mm
or more)
Horizontal or
upward gradient
Drain hose (accessories)
VP30 or more (O.D 38 mm or more)
Downward gradient 1/100 or more
Prohibited
- (06-69) -
Air bleeding
Rise
Trap
Drain hose is not used
5. Drain connection