Fujitsu AJ 126LELDH Series Design & Technical Manual page 778

Hide thumbs Also See for AJ 126LELDH Series:
Table of Contents

Advertisement

¢ Maximum connectable number of remote controller (2-wire
type)
Maximum connectable number of remote controller (2-wire type) is limited by cable size and maxi-
mum cable length.
Maximum connectable number of remote controller (2-wire type)
Cable size (S)
AWG
16
18
(1.25 > S ≥ 0.75)
20
(0.75 > S ≥ 0.5)
22
(0.5 > S ≥ 0.3)
4-4. Controller cable
2
L ≤ 100 m
mm
1.25
0.75
0.5
0.3
Total cable length (L)
100 m ≤ L ≤ 250 m
4
4
4
4
4
2
4
1
- (06-64) -
250 m ≤ L ≤ 500 m
4
2
2
1
4. Wiring design

Hide quick links:

Advertisement

Table of Contents
loading