2-6. Piping design example

¢ Example 1
Outdoor
unit
28.0 kW
b
24.4 kW
BP1
BP2
a1
1
3.6 kW
Indoor
unit
• System configuration
Indoor unit
1
2
3
4
5
6
7
8
Outdoor unit
1
• Capacity ratio
(Total capacity of indoor unit)/(Total capacity of outdoor unit)
= 28.0 / 22.4 = 125.0% (Within 50% to 150%)
• Selection of Separation tube
Branch kit no.
BP1
BP2
BP3
BP4
BP5
BP6
BP7
2-6. Piping design example
a
Total cooling capacity of indoor units connected downwards to the pipe
c
d
20.8 kW
17.2 kW
BP3
BP4
b1
c1
2
3
3.6 kW
3.6 kW
Indoor
Indoor
unit
unit
Total capacity
Total capacity
e
f
13.6 kW
10.0 kW
BP5
BP6
d1
e1
4
5
3.6 kW
3.6 kW
Indoor
Indoor
unit
unit
Model name
ARXD012GLEH
ARXD012GLEH
ARXD012GLEH
ARXD012GLEH
ARXD012GLEH
ARXD012GLEH
ARXD012GLEH
ARXD009GLEH
Model name
AJ072LELDH
Model name
UTP-AX090A
UTP-AX054A
- (06-29) -
g
h
6.4 kW
2.8 kW
BP7
f1
g1
6
7
3.6 kW
3.6 kW
2.8 kW
Indoor
Indoor
Indoor
unit
unit
Capacity (kW)
3.6
3.6
3.6
3.6
3.6
3.6
3.6
2.8
28.0
Capacity (kW)
22.4
22.4
Quantity
3
4
8
unit
2. Piping design