Fujitsu AJ 126LELDH Series Design & Technical Manual page 737

Hide thumbs Also See for AJ 126LELDH Series:
Table of Contents

Advertisement

• Pipe size table "A"
Between outdoor unit and the first separation tube (header)
– Standard
Outdoor unit
HP
model code
8
072
10
096
12
108
14
126
16
144
18
162
– Condition 1: Total indoor unit capacity ratio > 110%
Outdoor unit
HP
model code
8
072
10
096
12
108
14
126
16
144
18
162
– Condition 2: Between outdoor unit and first separation tube or header > 70 m (229 ft)
Outdoor unit
HP
model code
8
072
10
096
12
108
14
126
16
144
18
162
2-3. Pipe size
Outdoor unit cooling
capacity
kW
22.4
28.0
33.5
40.0
45.0
50.0
Outdoor unit cooling
capacity
kW
22.4
28.0
33.5
40.0
45.0
50.0
Outdoor unit cooling
capacity
kW
22.4
28.0
33.5
40.0
45.0
50.0
- (06-23) -
Outside diameter
Liquid pipe
mm (in)
9.52 (3/8)
9.52 (3/8)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
Outside diameter
Liquid pipe
mm (in)
9.52 (3/8)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
Outside diameter
Liquid pipe
mm (in)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
12.70 (1/2)
Gas pipe
19.05 (3/4)
22.22 (7/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
Gas pipe
19.05 (3/4)
22.22 (7/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
Gas pipe
22.22 (7/8)
22.22 (7/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
28.58 (1-1/8)
2. Piping design