• Outdoor unit connection interface (CN135) or touch panel controller connection interface
(TM201 CH1) to electricity meter
Item
Interface
Specifications
Units
Pulse
Constant
Line length restriction
Wiring specification
Line length restriction
Wiring specifications
1
*
Pulse signal: normally OFF (open), ON (closed) when shorted
2
*
When affected by interference by induction, select shielded CVV cable (CVV-S cable). This is
because copper shielding tape is wrapped around CVV cable and induction interference from ad-
jacent power cables is alleviated and normal communication is maintained. In addition, when the
wiring is outdoors, select weather resistance cable.
3
*
Use cable in accordance with local regulations and rules for cable.
• Number of installing electricity meters
Item
Number of installing electricity
meters
2-30. Electricity charge apportionment setting (System controller, Touch panel
controller)
Specifications
Dry contact "a" contacts
Width: 50 ms or more
Interval: 50 ms or more
1 kWh/pulse (pulse units) recommended.
Considering the electricity meters available in
some countries, use of electricity meters with
3,200 pulse/kWh (pulse constant) or less
pulses are possible.
150 m or less
Control and instrumentation cable: CVV-S
(Control-use Vinyl insulated Vinyl sheathed
2
cable – Shielding) *
2
2-conductor: 1.25 mm
25 m or less
2 core, twisted pair, 0.33 mm
Specifications
Max. 200
- (07-156) -
"a" contacts: ON when shorted
1
*
Between electricity meter and
outdoor unit
Between electricity meter and
2
3
touch panel controller
(22 AWG) *
Per site (include Max. 4 VRF
systems)
Remarks
Remarks
2. Function settings