Fujitsu AJ 126LELDH Series Design & Technical Manual page 625

Hide thumbs Also See for AJ 126LELDH Series:
Table of Contents

Advertisement

¢ Dimensions
¢ Specifications
Power supply
Power source frequency
Input power
Temperature
Humidity
Dimensions (H × W × D)
Weight
Fuse capacity
 Wiring specifications
Use
Power cable
(using remote
control cable)
Transmission cable
Remote controller
cable
(2-wire type)
Remote controller
cable
(3-wire type)
3-2. Network converter (UTY-VTGXV)
Hole pitch
4 × 20 = 80
5-Ø13
For dust proof bushing
4-Ø5
For M4 × 16 mm screws
Operating
Packaged
Packaged
Cable size
2
0.5 to 1.25 mm
60245 IEC 57 or equivalent
(20 to 16 AWG)
2
0.33 mm
Non-polar 2 core, twisted pair
(22 AWG)
2
0.33 to 1.25 mm
(22 to 16 AWG)
2
0.33 mm
(22 AWG)
- (05-125) -
10
59
Ø22
For conduit
2-Ø5
For M4 × 16 mm
screws
225
54
241
Hole pitch
260
V
Hz
W
°C
°C
%
mm
g
A
Wire type
LEVEL 4 (NEMA)
solid core shielded
Non-polar 2 core
Polar 3 core
Unit: mm
1 Ø AC 208—240
50/60
3.0
0 to 46
-10 to 60
0 to 95 (RH)
No condensation
54 × 260 × 150
1,100
2
Remarks
1 Ø AC 208—240 V 50/60 Hz,
2 wire + ground (Always ground
the unit)
LonWorks compatible cable
Use sheathed PVC cable or
shielded cable in accordance
with the regional cable standard.