• TM201 (CN412): Apply voltage terminal
When a power supply must be provided at the input device you want to connect, use the Apply
voltage terminal TM201 (CN412).
Connection example 1: When the switch is connected
Connection example 2: When the electricity meter is connected
1
Make the power supply DC12 to 24 V. Select a power supply capacity with an ample sur-
*
:
plus for the connected load.
2
Do not impress a voltage exceeding 24 V across K1-K2.
*
:
3
The allowable current is DC 10 mA or less. (Recommended: DC 5 mA)
*
:
Provide a load resistance such that the current becomes DC10 mA or less.
Select very low current use contacts (usable at DC 12 V, DC 1 mA or less).
A twisted pair cable 0.33 mm
 Selecting the function
The function of the external input terminals is disabled at the time of factory shipment. Select the
function to be used by installer setting of application.
Turn on the power and select by installer setting after starting the application.
Emergency stop
Electricity meter
4-1. Touch panel controller
1
*
DC power supply
12 to 24 V
3
*
*
3
*
1
*
DC power supply
12 to 24 V
2
(22 AWG) should be used. (Maximum cable length: 25 m)
All on/All off
PCB
TM201
2
PCB
TM201
2
*
- (08-29) -