Chapter 3 Rack Installation
3.1 Installing Power Distribution Unit (For Regions other than EMEA&I)
The four M6 screw positions for the brackets are determined relative to the power distribution unit base
line.
The M6 screws should be inserted in the 1st and 3rd holes above the base line.
3rd position
(M6 screw)
1st position
(M6 screw)
3
Install the power distribution unit in the rack.
Fasten the power distribution unit to the bracket with the two M3 screws removed in
M3 screw
(Rear rack pillars)
4
Attach the blank panel to the front side of the rack.
The blank panel should be attached at the same height as the power distribution unit.
Power distribution unit
(Rear rack pillars)
ETERNUS DX80 S2/DX90 S2 Disk storage system User's Guide -Installation-
(Rear rack pillars)
[Left]
1U
Power distribution unit
Base line of
power distribution unit
Brackets
M3 screw
(Front rack pillars)
49
Copyright 2013 FUJITSU LIMITED
[Right]
3rd position
(M6 screw)
1st position
(M6 screw)
Blank panel
Step
1.
End of procedure
P3AM-4832-07ENZ0