Chapter 4 Connecting Cables
4.5 Power Cord Connection
4.5.2
When 1U Power Distribution Unit is Installed (For Regions other than EMEA&I)
The following procedure explains how to connect the power cord when a 1U power distribution unit is
installed.
To help with power cord management and prevent incorrect connections, attach labels to the power cords
and make a note of connection origins and destinations.
Procedure
1
Remove the power cord clamp from the power distribution unit.
Power distribution unit
2
Connect the power distribution unit outlets and power supply unit inlets with the power
cords (AC output cables, 3m) provided with the power distribution unit.
The procedures to connect the power supply unit is same as the
Distribution Units are Installed" (page
Each enclosure has two power supply units (PSU#0 and PSU#1). The power cords must be connected
to the inlets of both power supply units.
The following figure shows an example of AC output cable connection:
PSU#0 Inlet
ETERNUS DX80 S2/DX90 S2 Disk storage system User's Guide -Installation-
Drive Enclosure 1
Controller Enclosure
PSU#0 Inlet
Power distribution unit
Outlet
Outlet
OUTPUT #0-1
OUTPUT #0-2
: Connect between the OUTPUT#0-n of the power distribution unit
and the PSU#0 inlets of the ETERNUS DX Disk storage system
: Connect between the OUTPUT#1-n of the power distribution unit
and the PSU#1 inlets of the ETERNUS DX Disk storage system
Copyright 2013 FUJITSU LIMITED
78).
PSU#1 Inlet
PSU#1 Inlet
Outlet
OUTPUT #1-1
Outlet
OUTPUT #1-2
81
Power cord clamps
Step 1
in
"4.5.1 When no Power
P3AM-4832-07ENZ0