Control Connections

Control Connection Specifications

Analog Inputs and
(Digital Outputs)
Cable Specifications

Control Cables

General Recommendations

Use multi-core cables with a braided copper wire screen, temperature rated at 60 °C
(140 °F) or above:
Example: JAMAK by Draka NK Cables
At the drive end, twist the screen together into a bundle not longer than five times its
width and connected to terminal X1-1 (for digital and analog I/O cables) or to either
X1-28 or X1-32 (for RS485 cables). Leave the other end of the cable shield
unconnected.
Route control cables to minimize radiation to the cable:
• Route as far away as possible from the input power and motor cables (at least
20 cm (8 in)).
• Where control cables must cross power cables make sure they are at an angle as
near 90° as possible.
• Stay at least 20 cm (8 in) from the sides of the drive.
Use care in mixing signal types on the same cable:
• Do not mix analog and digital input signals on the same cable.
• Run relay-controlled signals as twisted pairs (especially if voltage > 48 V). Relay-
controlled signals using less than 48 V can be run in the same cables as digital
input signals.
Note! Never mix 24 VDC and 115/230 VAC signals in the same cable.
Technical Data
See table heading "Hardware Description" on page 17.
Outputs
Digital Inputs
Digital input impedance 1.5 kΩ. Maximum voltage for digital inputs is 30 V.
• Max. contact voltage: 30 V DC, 250 V AC
• Max. contact current / power: 6 A, 30 V DC; 1500 VA, 250 V AC
• Max. continuous current: 2 A rms (cos ϕ = 1), 1 A rms (cos ϕ = 0.4)
Relays
• Minimum load: 500 mW (12 V, 10 mA)
• Contact material: Silver-nickel (AgN)
• Isolation between relay digital outputs, test voltage: 2.5 kV rms, 1 minute
See "Control Terminals Table" on page 17.