ACS550 User's Manual
Group 26: Motor Control
Code Description
2601 FLUX OPTIMIZATION
Changes the magnitude of the flux depending on the actual load. Flux Optimization can reduce the total energy
consumption and noise, and should be enabled for drives that usually operate below nominal load.
0 = Disables the feature.
1 = Enables the feature.
2602 FLUX BRAKING
Provides faster deceleration by raising the level of
magnetization in the motor when needed, instead of
limiting the deceleration ramp. By increasing the flux in
the motor, the energy of the mechanical system is
changed to thermal energy in the motor.
0 = Disables the feature.
1 = Enables the feature.
2603 IR COMP VOLT
Sets the IR compensation voltage used for 0 Hz.
• Requires parameter 9904
(
:
).
SCALAR
SPEED
• Keep IR compensation as low as possible to prevent
overheating.
• Typical IR compensation values are:
380...480 V Units
P
(kW)
3
N
IR comp (V)
18
2604 IR COMP FREQ
Sets the frequency at which IR compensation is 0 V (in
% of motor frequency).
2605 U/f RATIO
Selects the form for the U/f (voltage to frequency) ratio below field weakening point.
1 =
– Preferred for constant torque applications.
LINEAR
2 =
– Preferred for centrifugal pump and fan applications. (Square is more silent for most operating
SQUARE
frequencies.)
2606 SWITCHING FREQ
Sets the switching frequency for the drive. Also see parameter 2607
Derating" on page 217.
• Higher switching frequencies mean less noise.
• The 12 kHz switching frequency is available only if parameter 9904
• The 12 kHz switching frequency is available only on frame sizes R1...R6
= 3
MOTOR CTRL MODE
7.5
15
37
132
15
12
8
3
Braking
Torque (%)
120%
W/O Flux Braking
80
1
40
2
0
5
10
120%
With Flux Braking
80
1
40
2
3
4
5
0
5
10
IR Compensation
• When enabled, IR Compensation provides an extra
voltage boost to the motor at low speeds. Use IR
Compensation, for example, in applications that require a
high breakaway torque.
Motor
Voltage
P 2603
SW FREQ CTRL
MOTOR CTRL MODE
Rated Motor Power
2.2 kW
1
15 kW
2
37 kW
3
75 kW
4
250 kW
5
3
4
5
20
30
40
f (Hz)
20
30
40
A
A = IR Compensated
B = No compensation
f (Hz)
B
P 2604
and "Switching Frequency
= 3 (
:
).
SCALAR
SPEED
Start-Up
101
50
50
f (Hz)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-u1

Table of Contents