Group 14: Relay Outputs
This group defines the condition that activates each of the relay outputs.
Code Description
1401 RELAY OUTPUT 1
Defines the event or condition that activates relay 1 – what relay output 1 means.
0 =
– Relay is not used and is de-energized.
NOT SEL
1 =
– Energize relay when drive is ready to function. Requires:
READY
• Run enable signal present.
• No faults exist.
• Supply voltage is within range.
• Emergency Stop command is not on.
2 =
– Energize relay when the drive is running.
RUN
3 =
(-1) – Energize relay when power is applied. De-energizes when a fault occurs.
FAULT
4 =
– Energize relay when a fault is active.
FAULT
5 =
– Energize relay when an alarm is active.
ALARM
6 =
– Energize relay when motor rotates in reverse direction.
REVERSED
7 =
– Energize relay when drive receives a start command (even if Run Enable signal is not present). De-
STARTED
energized relay when drive receives a stop command or a fault occurs.
8=
1
– Energize relay when first supervised parameter (3201) exceeds the limit (3203).
SUPRV
OVER
• See "Group 32: Supervision" starting on page 109.
9 =
1
– Energize relay when first supervised parameter (3201) drops below the limit (3202).
SUPRV
UNDER
• See "Group 32: Supervision" starting on page 109.
10 =
2
– Energize relay when second supervised parameter (3204) exceeds the limit (3206).
SUPRV
OVER
• See "Group 32: Supervision" starting on page 109.
11 =
2
SUPRV
UNDER
• See "Group 32: Supervision" starting on page 109.
12 =
3
– Energize relay when second supervised parameter (3207) exceeds the limit (3209).
SUPRV
OVER
• See "Group 32: Supervision" starting on page 109.
13 =
3
SUPRV
UNDER
• See "Group 32: Supervision" starting on page 109.
14 =
– Energize relay when the output frequency is equal to the reference frequency.
AT SET POINT
15 =
(
) – Energize relay when the drive is in a fault condition and will reset after the programmed auto-reset
FAULT
RST
delay.
• See parameter 3103 delay time.
16 =
/
– Energize relay when fault or alarm occurs.
FLT
ALARM
17 =
– Energize relay when external control is selected.
EXT CTRL
18 =
2
– Energize relay when
REF
SEL
19 =
– Energize relay when a constant speed is selected.
CONST FREQ
20 =
– Energize relay when reference or active control place is lost.
REF LOSS
21 =
OVERCURRENT
22 =
OVERVOLTAGE
23 =
– Energize relay when a drive overtemperature alarm or fault occurs.
DRIVE TEMP
24 =
UNDERVOLTAGE
25 =
1
– Energize relay when
AI
LOSS
26 =
2
– Energize relay when
AI
LOSS
27 =
– Energize relay when a motor overtemperature alarm or fault occurs.
MOTOR TEMP
28 =
– Energize relay when a stall alarm or fault exists.
STALL
29 =
– Energize relay when an underload alarm or fault occurs.
UNDERLOAD
30 =
– Energize relay when the PID sleep function is active.
PID SLEEP
31 =
– Use relay to start/stop motor in PFC control (See Group 81: PFC Control).
PFC
• Use this option only when PFC control is used.
• Selection activated / deactivated when drive is not running.
32 =
– Energize relay when PFC autochange operation is performed.
AUTOCHANGE
• Use this option only when PFC control is used.
33 =
– Energize relay when the motor is magnetized and able to supply nominal torque (motor has
FLUX READY
reached nominal magnetizing).
34 =
2 – Energize relay when User Parameter Set 2 is active.
USER S
Start-Up
– Energize relay when second supervised parameter (3204) drops below the limit (3205).
– Energize relay when second supervised parameter (3207) drops below the limit (3208).
2 is selected.
EXT
– Energize relay when an overcurrent alarm or fault occurs.
– Energize relay when an overvoltage alarm or fault occurs.
– Energize relay when an undervoltage alarm or fault occurs.
1 signal is lost.
AI
2 signal is lost.
AI
ACS550 User's Manual