Maintenance
Warning! Read "Safety" on page 3 before performing any maintenance on the
equipment. Ignoring the safety instructions can cause injury or death.

Maintenance Intervals

If installed in an appropriate environment, the drive requires very little maintenance.
This table lists the routine maintenance intervals recommended by ABB.
Heatsink temperature check
and cleaning
Main cooling fan replacement
Internal enclosure cooling fan
replacement
(IP 54/UL Type 12 units)
Capacitor change
(Frame sizes R5 and R6)
Replace battery in the Assistant
control panel

Heatsink

The heatsink fins accumulate dust from the cooling air. Since a dusty heatsink is less
efficient at cooling the drive, overtemperature faults become more likely. In a
"normal" environment (not dusty, not clean) check the heatsink annually, in a dusty
environment check more often.
Clean the heatsink as follows (when necessary):
1. Remove power from drive.
2. Remove the cooling fan (see section "Main Fan Replacement" on page 212).
3. Blow clean compressed air (not humid) from bottom to top and simultaneously use a
vacuum cleaner at the air outlet to trap the dust.
Note: If there is a risk of the dust entering adjoining equipment, perform the cleaning
in another room.
4. Replace the cooling fan.
5. Restore power.
Maintenance
Depends on the dustiness of the
environment (every 6...12
months)
Every five years
Every three years.
Every ten years
Every ten years
Interval
See "Heatsink" on page 211.
See "Main Fan Replacement"
on page 212.
See "Internal Enclosure Fan
Replacement" on 213.
See "Capacitors" on page 213.
See "Battery" on page 214.