Code
Name
Group 99: Start-Up Data
9901
LANGUAGE
9902
APPLIC MACRO
9904
MOTOR CTRL MODE
9905
MOTOR NOM VOLT
9906
MOTOR NOM CURR
9907
MOTOR NOM FREQ
9908
MOTOR NOM SPEED
9909
MOTOR NOM POWER
9910
MOTOR ID RUN
Group 01: Operating Data
0102
SPEED
0103
OUTPUT FREQ
0104
CURRENT
0105
TORQUE
0106
POWER
0107
DC BUS VOLTAGE
0109
OUTPUT VOLTAGE
0110
DRIVE TEMP
0111
1
EXTERNAL REF
0112
2
EXTERNAL REF
0113
CTRL LOCATION
0114
(
)
RUN TIME
R
0115
(
)
KWH COUNTER
R
0116
APPL BLK OUTPUT
0118
1-3
DI
STATUS
0119
4-6
DI
STATUS
0120
1
AI
0121
2
AI
0122
1-3
RO
STATUS
0123
4-6
RO
STATUS
0124
1
AO
0125
2
AO
Parameters can be modified only when the drive is stopped.
Range
0...13
-3...8
1=
:
, 2=
VECTOR
SPEED
VECTOR
3=
:
SCALAR
SPEED
115...345 V
01: 200...600 V /
U1: 230...690 V
0.2*I
...2.0*I
2hd
2hd
10.0...500 Hz
50...30,000 rpm
0.2...3.0*P
hd
0 =
, 1=
OFF
ON
0...30000 rpm
0.0...500.0 Hz
0...2.0*I
2hd
-200...200%
-2.0...2.0*P
hd
0...2.5*V
dN
0...2.0*V
dN
0...150 °C
0...30000 rpm / 0...500 Hz
0...100% (0...600% for torque)
0 = local, 1 = ext1, 2 = ext2
0...9999 h
0...9999 kWh
0...100% (0...600% for torque)
000...111 (0...7 decimal)
000...111 (0...7 decimal)
0...100%
0...100%
000...111 (0...7 decimal)
000...111 (0...7 decimal)
0...20 mA
0...20 mA
Resolution
1
1
:
,
1
TORQUE
1 V
1 V
0.1 A
0.1 Hz
1 rpm
01: 0.1 kW /
U1: 0.1 HP
1
1 rpm
0.1 Hz
0.1 A
0.1%
0.1 kW
1 V
1 V
0.1 °C
1 rpm / 0.1 Hz -
0.1%
1
1 h
1 kWh
0.1%
1
1
0.1%
0.1%
1
1
0.1 mA
0.1 mA
Default
User S
0
1
3
230 V
01: 400 V /
U1: 460 V
1.0*I
2hd
01: 50 Hz /
U1: 60 Hz
Size dependent
1.0 * P
hd
0
-
-
-
-
-
-
-
-
-
-
0 h
-
-
-
-
-
-
-
-
-
-
Start-Up