Application Macro: Hand-Auto - ABB ACS550-01 User Manual

Drive low voltage ac drives
Hide thumbs Also See for ACS550-01:
Table of Contents

Advertisement

ACS550 User's Manual

Application macro: Hand-Auto

This macro provides an I/O configuration that is typically used in HVAC applications.
To enable, set the value of parameter 9902 to 5 (
Note! Parameter 2108
Connection example:
• Two analog references (AI1, 2)
• Start/stop – hand/auto (DI1, 6)
• Direction – hand/auto (DI2, 5)
• Control location selection (DI3)
• Run enable (DI4)
START INHIBIT
X1
Signal cable shield (screen)
1
SCR
External reference 1: 0
2
AI1
Analog input circuit common
3
AGND
Reference voltage 10 VDC
4
10V
External reference 2: 0
5
AI2
Analog input circuit common
6
AGND
Motor output speed: 0
7
AO1
Output current: 0
8
AO2
Analog output circuit common
9
AGND
Auxiliary voltage output +24 VDC
10 24V
Auxiliary voltage output common
11 GND
Digital input common for all
12 DCOM
13 DI1
Start/Stop (Hand): Activation starts the drive
14 DI2
Forward/Reverse (Hand): Activation reverses rotation direction
15 DI3
EXT1/EXT2 Selection: Activation selects auto control
16 DI4
Run enable: Deactivation always stops the drive
17 DI5
Forward/Reverse (Auto): Activation reverses rotation direction
18 DI6
Start/Stop (Auto): Activation starts the drive
19 RO1C
Relay output 1, programmable
20 RO1A
Default operation:
Ready =>19 connected to 21
21 RO1B
22 RO2C
Relay output 2, programmable
23 RO2A
Default operation:
Running =>22 connected to 24
24 RO2B
25 RO3C
Relay output 3, programmable
26 RO3A
Default operation:
Fault (-1) =>25 connected to 27
27 RO3B
(Fault => 25 connected to 26)
Input signals
HAND
must remain in the default setting, 0 (
...
10 V (Hand Control)
...
20 mA (Auto Control)
...
20 mA
...
20 mA
Output signals
• Analog output AO1: Speed
• Analog output AO2: Current
• Relay output 1: Ready
• Relay output 2: Running
• Relay output 3: Fault (-1)
/
).
AUTO
OFF
Jumper Setting
J1
...
AI1: 0
AI2: 0(4)
47
).
10 V
...
20 mA
Start-Up

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: