Application Macro: 3-Wire - ABB ACS550-01 User Manual

Drive low voltage ac drives
Hide thumbs Also See for ACS550-01:
Table of Contents

Advertisement

44

Application Macro: 3-wire

This macro is used when the drive is controlled using momentary push-buttons, and
provides three (3) constant speeds. To enable, set the value of parameter 9902 to 2
(3-
WIRE
Note! When the stop input (
buttons are disabled.
Connection example:
• Analog reference (AI1)
• Start, stop and direction (DI1,2,3)
• Constant speed selection (DI4,5)
Start-Up
).
DI
X1
1
SCR
Signal cable shield (screen)
2
AI1
External speed reference 1: 0
3
AGND
Analog input circuit common
4
10V
Reference voltage 10 VDC
5
AI2
Not used
6
AGND
Analog input circuit common
7
AO1
Motor output speed: 0
8
AO2
Output current: 0
9
AGND
Analog output circuit common
Auxiliary voltage output +24 VDC
10 24V
Auxiliary voltage output common
11 GND
Digital input common for all
12 DCOM
13 DI1
Start: Momentary activation with DI2 activated starts the drive
14 DI2
Stop: Momentary deactivation stops the drive
15 DI3
Fwd/Rev: Activation reverses rotation direction
16 DI4
Constant speed selection
17 DI5
Constant speed selection
18 DI6
Not used
19 RO1C
Relay output 1, programmable
Default operation:
20 RO1A
Ready =>19 connected to 21
21 RO1B
22 RO2C
Relay output 2, programmable
Default operation:
23 RO2A
Running =>22 connected to 24
24 RO2B
25 RO3C
Relay output 3, programmable
Default operation:
26 RO3A
Fault (-1) =>25 connected to 27
27 RO3B
(Fault => 25 connected to 26)
Input signals
2) is deactivated (no input), the control panel start/stop
...
10 V
...
20 mA
...
20 mA
1
1
Output signals
• Analog output AO1: Speed
• Analog output AO2: Current
• Relay output 1: Ready
• Relay output 2: Running
• Relay output 3: Fault (-1)
ACS550 User's Manual
Note 1. Code:
0 = open, 1 = connected
DI4 DI5
Output
0
0
Reference through AI1
1
0
CONSTANT SPEED
0
1
CONSTANT SPEED
1
1
CONSTANT SPEED
Jumper Setting
J1
...
AI1: 0
AI2: 0(4)
1 (1202)
2 (1203)
3 (1204)
10 V
...
20 mA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs550-u1