ScreenMaster RVG200
Paperless recorder
Historical logs
Types:
Alarm / event, totalizer and audit
logs
Number of records
Up to 500 in internal memory
in each historical
Oldest data is automatically
log:
overwritten by new data when
log is full
Log entry events
Information recorded in log /
on screen
Date & time of event
Type of event
Tag
Source tag
Alarm trip value & units of
measure
Alarm state
Alarm acknowledgement state
Operator ID
Description
Batch total and units of
measurement*
Maximum, minimum and average
values plus units*
Secure total
* If Totalizer option fitted and selected
140
Alarm / event log
Totalizer log
• Alarm state changes
• User defined logging intervals
• Operator messages
• Totalizer stop / start, reset, wrap
• Power up / down
In log
On screen
—
—
—
—
—
—
—
—
—
—
—
In log
On screen
—
—
—
—
—
—
—
—
—
—
—
—
8 Specification
Audit log
• Configuration / calibration changes
• System events
• Errors, operator actions
In log
On screen
—
—
—
—
—
—
—
—
OI/RVG200-EN
—
—
—
—
—
—
—
—