ABB ScreenMaster RVG200 Operating Instructions Manual page 44

Paperless recorder
Hide thumbs Also See for ScreenMaster RVG200:
Table of Contents

Advertisement

ScreenMaster RVG200
Paperless recorder
Screen Interval
Chart views only
Sample rate setting
More than 1 second, less than 4 seconds
More than 4 seconds, less than 8 seconds
More than 8 seconds, less than 12 seconds
More than 12 seconds, less than 28 seconds
Table 4.1 Sample rates and screen intervals
42
Note. Greyed-out if the Screen interval select menu enable is not selected
– see page 83.
Touch to change the amount of data displayed on the screen. A longer
screen interval displays more data, a shorter screen interval displays data
over a shorter time period, but in more detail. In both cases, the full trace is
preserved by plotting the maximum and minimum samples for each display
point.
Longer interval =
better overview
The screen intervals available in the menu are determined by the faster of
the primary and secondary sample rates set for the process group during
configuration – see Section 7.8.1, page 80.
Table 4.1 shows the relationship between sample rate and screen interval
for the vertical and horizontal chart views.
Note.
A 'Please Wait' message appears in the status bar while the recorder
retrieves data from storage.
Selecting a different screen interval does not affect the rate at which
data is sampled.
When in historical review mode, changing the screen interval causes
the time at the cursor position to change.
<1 second
More than 28 seconds
Maximum screen interval
Vertical chart view
Up to 1 hour / screen
Up to 12 hours / screen
Up to 1 days / screen
Up to 2 days / screen
Up to 3 days / screen
Up to 7 days / screen
4 Operation
Shorter interval =
more detail
Horizontal chart view
Up to 1.5 hours / screen
Up to 21 hours / screen
Up to 1.5 days / screen
Up to 3 days / screen
Up to 4.5 days / screen
Up to 12 days / screen
OI/RVG200-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents