7.10.9 Comms digital input

Note. This tab is displayed only if only if Implementation on the MODBUS TCP tab is set to Master –
see page 121.
Comms digital I/P
Comms digital I/P
Protocol
Note. The following parameter is displayed only if Protocol is set to TCP.
IP-address
Note. The following parameters are displayed only if Protocol is set to RTU.
RTU Address
Gateway
Note. The remaining parameters are displayed only if Protocol is set to TCP or RTU.
Register Number
Type
OI/RVG200-EN
Select the communications digital input to hold the status from the
nominated slave device.
Select the communications protocol to be used by the recorder to
communicate with a nominated slave device:
None
communications digital channel unused.
TCP
MODBUS Transmission Control Protocol.
RTU
access a Remote Terminal Unit (RTU) via MODBUS TCP
gateway.
Enter the IP address assigned to the slave device.
Enter the RTU address assigned to the remote unit (1 to 247).
Set the IP address for the MODBUS TCP gateway required to
communicate with the RTU.
Note. This setting is always required to access a RTU via Ethernet.
Enter the register number to be read or written to in the slave device.
Select the register type, Input Status or Coil Status.
7 Configuration