ScreenMaster RVG200
Paperless recorder
3.4 Analog / digital input module
Note. Tighten analog / digital input terminal screws to a torque of 0.1 Nm (0.9 lbf.in).
3.4.1 Thermocouple
Use the correct compensating cable between the thermocouple and the terminals – see Table 3.1.
Automatic cold junction compensation (ACJC) is incorporated but an independent cold (reference) junction
may be used.
Thermocouple type
Ni-Cr / Ni-Al (K)
Brown Blue
Ni-Cr / Cu-Ni (E)
Nicrisil / Nisil (N)
Orange Blue Orange Orange Red Orange
Pt / Pt-Rh (R and S)
White Blue Green
Pt-Rh / Pt-Rh (B)
Cu / Cu-Ni (T)
White Blue
Fe / Con (J)
Yellow Blue Black
Fe / Con (DIN 43710)
Table 3.1 Thermocouple compensating cable
3.4.2 Resistance thermometer (RTD)
On applications requiring long leads it is preferable to use a 3-lead resistance thermometer.
If 2-lead resistance thermometers are used, each input must be calibrated to take account of the lead
resistance.
18
BS1843
ANSI MC 96.1
+
–
Case
+
Red
Yellow Red Yellow
–
Black Red Green
–
Blue
Blue
White Red Black
–
Compensating cable
DIN 43714
–
Case
+
Red
Green Green Green White Green *
–
Red
White White Orange White Orange *
–
Red
Blue
Red
Brown Brown Brown White Brown *
Red
Blue
DIN 43710
–
Blue /
Blue
red
3 Installation
BS4937 Part No.30
–
Case
+
–
Violet White Violet *
–
Pink
White
–
Grey
White
Blue
Black White Black *
* Case Blue for intrinsically safe circuits
Blue
OI/RVG200-EN
–
Case
Pink *
Grey *
–