ABB ScreenMaster RVG200 Operating Instructions Manual page 94

Paperless recorder
Hide thumbs Also See for ScreenMaster RVG200:
Table of Contents

Advertisement

ScreenMaster RVG200
Paperless recorder
Engineering range *
Low
High
**
Units
* If this parameter is changed, internally-recorded data files are recreated and unarchived data is lost.
** Due to the display resolution, if more than 2 channels are assigned to a group, engineering units featuring
a superscript 3 character (for example, m
92
Select the display characteristics of the input.
Specify the display range and units of the engineering value
corresponding to the electrical high and low values, within the limits
defined in Table 7.3.
THC / RTD type
B
E
J
K
L
N
R & S
T
Pt100
Power 5/2
Power 3/2
Square Root
Custom Linearizer 1
Custom Linearizer 2
Linear
Table 7.3 Limits of engineering ranges
3
) may not be displayed correctly in the Chart views.
°C
Minimum Maximum Minimum Maximum
–18
1800
–100
900
–100
900
–100
1300
–100
900
–200
1300
–18
1700
–250
300
–200
600
–99999 to +999999
7 Configuration
°F
0
3270
–140
1650
–140
1650
–140
2350
–140
1650
–325
2350
0
3090
–400
570
–325
1100
OI/RVG200-EN