Figure 6-5 Generic Wiring Diagram - ABB XSeries G4 6200 User Manual

Flow computer
Table of Contents

Advertisement

To Third Party
Analog Devices
SEE SHEET 2
6.2.9.1
Analog Inputs
The input range is 0-10 volts for the three 0-5V analog inputs (AI1, AI2 and AI3).
The inputs have a low pass filter -3 dB point of 100Hz. The sourcing device must
be capable of driving 10K input impedance.
As shown below, an external 250-255 OHM resistor is required (across + and –
input) to convert a 0/4-20 mA signal to a 0/1-5V compatible input.
The analog inputs must be defined in PCCU32.
2104349 rev. AD
DB-9 Connector to XFCEX Board I/O
Expansion Connector (J2)
(Mounted on Back)
J3
J6
+ AI -
+ DI -
J8
RTD IN
I/O EXPANSION
RTD -
6
9
RTD +
1
RTD OUT
SHIELD
J2
RTD
1
AI1(+)
I/O Daughter Card
AI1(-)
P/N: 2102458
AI2(+)
AI2(-)
J21
AI3(+)
MMI
AI3(-)
ON
OFF
AOut(+)
4
1
3
1
AOut(-)
SW2
2
J3
8
1
J1
COMM2
J20
1
2 3 4
5
To Third Party
Digital Output Devices
Figure 6–5 Generic Wiring Diagram
Analog Points
XFCEX Board (Ref)
J5
SECURITY
+ DO -
ON
J19
J2
1
COMM1
8
DI1(+)
DI1(-)
5
6
DI2(+)
5
DI2(-)
4
DI3(+)
3
4
3
2
1
DI3(-)
2
OFF
DI4(+)
1
ON
DI4(-)
SW1
2
-
J16
8
1
PWR
+
8
6 7 8
The Digital Outputs have a maximum "ON"
resistance of 2.5Ω which can switch 48V AC/
DC at up to 100mA. The outputs are isolated
(AC voltage for 1 minute at 25°C, RH=60%
between input and output) from each other as
well as the control circuit by 1500Vrms.
The DI/PI inputs will accept sensor inputs
which meet the IEC-60947-5-6 electrical
characteristics.