ABB ACSM1 Firmware Manual page 150

Speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

150
(3) LAST SPEED
50.03 COMM LOSS T OUT
Defines the time delay before the action defined by parameter
Time count starts when the link fails to update the message.
0.3...6553.5 s
50.04 FBA REF1 MODESEL
Selects the fieldbus reference FBA REF1 scaling and the actual value, which is sent to the fieldbus
(FBA ACT1).
(0) RAW DATA
(1) TORQUE
(2) SPEED
(5) AUTO
50.05 FBA REF2 MODESEL
Selects the fieldbus reference FBA REF2 scaling.
See parameter
50.06 FBA ACT1 TR SRC
Selects the source for fieldbus actual value 1 when parameter
FBA REF2 MODESEL
Value pointer: Group and index
50.07 FBA ACT2 TR SRC
Selects the source for fieldbus actual value 2 when parameter
FBA REF2 MODESEL
Value pointer: Group and index
Parameters and firmware blocks
Protection is active. The drive generates alarm FIELDBUS COMM
and freezes the speed to the level the drive was operating at. The
speed is determined by the average speed over the previous 10
seconds.
WARNING! Make sure that it is safe to continue operation in
case of a communication break.
FW block:
Delay for fieldbus communication loss function.
FW block:
No scaling (i.e. data is transmitted without scaling). Source for the
actual value, which is sent to the fieldbus, is selected by parameter
50.06 FBA ACT1 TR
Fieldbus adapter module uses torque reference scaling. Torque
reference scaling is defined by the used fieldbus profile (e.g. with ABB
Drives Profile integer value 10000 corresponds to 100% torque
value). Signal
See the User's Manual of the appropriate fieldbus adapter module.
Fieldbus adapter module uses speed reference scaling. Speed
reference scaling is defined by the used fieldbus profile (e.g. with ABB
Drives Profile integer value 20000 corresponds to the value of
parameter
to the fieldbus as an actual value. See the User's Manual of the
appropriate fieldbus adapter module.
One of the above selections is chosen automatically according to the
currently active control mode. See parameter group
CTRL.
FW block:
50.04 FBA REF1
MODESEL.
FW block:
is set to
(0) RAW
FW block:
is set to
(0) RAW
FIELDBUS
(see above)
50.02 COMM LOSS FUNC
FIELDBUS
(see above)
SRC.
1.06 TORQUE
is sent to the fieldbus as an actual value.
25.02 SPEED
SCALING). Signal
FIELDBUS
(see above)
FIELDBUS
(see above)
50.04 FBA REF1 MODESEL
DATA.
FIELDBUS
(see above)
50.04 FBA REF1 MODESEL
DATA.
is taken.
1.01 SPEED ACT
is sent
34 REFERENCE
/
50.05
/
50.05