Mux; Sel - ABB ACSM1 Firmware Manual

Speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

288
Operation
Inputs
Outputs

MUX

(10055)
Illustration
Execution time
Operation
Inputs
Outputs

SEL

(10056)
Illustration
Execution time
Operation
Inputs
Outputs
Standard function blocks
The output (OUT) is the lowest input value (IN).
The input data type and the number of inputs (2...32) are selected by the user.
Input (IN1...IN32): INT, DINT, REAL, REAL24
Output (OUT): INT, DINT, REAL, REAL24
(DINT)
TLA1 1 msec
K
IN1
IN2
0.70 µs
The value of an input (IN) selected by the address input (K) is stored to the output
(OUT).
If the address input is 0, negative or exceeds the number of the outputs, the output is 0.
The input data type and number of inputs (2...32) are selected by the user.
Address input (K): DINT
Input (IN1...IN32): INT, DINT, REAL, REAL24
Output (OUT): INT, DINT, REAL, REAL24
(BOOL)
TLA1 1 msec
G
IN A
IN B
1.53 µs
The output (OUT) is the value of the input (IN) selected by the selection input (G).
If G = 0: OUT = IN A.
If G = 1: OUT = IN B.
The input data type is selected by the user.
Selection input (G): Boolean
Input (IN A, IN B): Boolean, INT, DINT, REAL, REAL24
Output (OUT): Boolean, INT, DINT, REAL, REAL24
MUX
79
(1)
OUT(79)
OUT
SEL
80
(1)
OUT(80)
OUT