Parameter
52.01 FBA DATA IN1
...
52.12 FBA DATA
IN12
53.01 FBA DATA
OUT1
...
53.12 FBA
DATA OUT12
Note: In the User's Manual of the fieldbus adapter module, the parameter group number is 3 or C for parameters
52.01...52.12
and 2 or B for parameters 53.01...53.12.
After the module configuration parameters have been set, the drive control
parameters (see section
when necessary.
The new settings will take effect when the drive is powered up the next time (before
powering off the drive, wait at least 1 minute), or when parameter
REFRESH is activated.

Drive control parameters

The Setting for fieldbus control column gives the value to use when the fieldbus
interface is the desired source or destination for that particular signal. The Function/
Information column gives a description of the parameter.
Parameter
10.01 EXT1 START
FUNC
10.04 EXT2 START
FUNC
24.01 SPEED REF1 SEL
24.02 SPEED REF2 SEL
32.01 TORQ REF1 SEL
32.02 TORQ REF ADD
SEL
16.07 PARAM SAVE
Setting for
fieldbus control
TRANSMITTED DATA SELECTION
0
Defines the data transmitted from drive to fieldbus controller.
4...6
Note: If the selected data is 32 bits long, two parameters are reserved
14...16
for the transmission.
101...9999
0
Defines the data transmitted from fieldbus controller to drive.
1...3
Note: If the selected data is 32 bits long, two parameters are reserved
11...13
for the transmission.
1001...9999
Drive control
Setting for
fieldbus control
CONTROL COMMAND SOURCE SELECTION
(3) FBA
Selects fieldbus as the source for the start and stop commands when
EXT1 is selected as the active control location.
(3) FBA
Selects fieldbus as the source for the start and stop commands when
EXT2 is selected as the active control location.
(3) FBA REF1
Fieldbus reference REF1 or REF2 is used as speed reference 1.
(4) FBA REF2
(3) FBA REF1
Fieldbus reference REF1 or REF2 is used as speed reference 2.
(4) FBA REF2
(3) FBA REF1
Fieldbus reference REF1 or REF2 is used as torque reference 1.
(4) FBA REF2
(3) FBA REF1
Fieldbus reference REF1 or REF2 is used for torque reference
(4) FBA REF2
addition.
SYSTEM CONTROL INPUTS
(0) DONE
Saves parameter value changes (including those made through
(1) SAVE
fieldbus control) to permanent memory.
Function/Information
parameters) must be checked and adjusted
Function/Information
Appendix A – Fieldbus control
315
51.27
FBA PAR