ABB ACSM1 Firmware Manual page 206

Speed and torque control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

206
Code
Alarm
(fieldbus code)
2031
ENCODER 1 CABLE
(0x7389)
2032
ENCODER 2 CABLE
(0x738A)
2033
D2D COMMUNICATION
(0x7520)
Programmable fault:
COMM LOSS FUNC
2034
D2D BUFFER
OVERLOAD
(0x7520)
Programmable fault:
COMM LOSS FUNC
2035
PS COMM
(0x5480)
2036
RESTORE
(0x630D)
2037
CUR MEAS
CALIBRATION
(0x2280)
2038
AUTOPHASING
(0x3187)
2039
EARTH FAULT
(0x2330)
Programmable fault:
EARTH FAULT
2041
MOTOR NOM VALUE
(0x6383)
Fault tracing
Cause
Encoder 1 cable fault detected.
Encoder 2 cable fault detected.
On the master drive: The drive
has not been replied to by an
activated follower for five
57.02
consecutive polling cycles.
On a follower drive: The drive
has not received new reference
1 and/or 2 for five consecutive
reference handling cycles.
Transmission of drive-to-drive
references failed because of
message buffer overflow.
57.02
Communication errors detected
between the JCU Control Unit
and the power unit of the drive.
Restoration of backed-up
parameters failed.
Current measurement
calibration will occur at next
start.
Autophasing will occur at next
start.
Drive has detected load
unbalance typically due to earth
fault in motor or motor cable.
46.05
The motor configuration
parameters are set incorrectly.
The drive is not dimensioned
correctly.
What to do
Check cable between FEN-xx interface and
encoder 1. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
90.10 ENC PAR
REFRESH.
Check cable between FEN-xx interface and
encoder 2. After any modifications in cabling,
re-configure interface by switching drive
power off and on, or by activating parameter
90.10 ENC PAR
REFRESH.
Check that all drives that are polled
(parameters
57.04
and 57.05) on the drive-to-
drive link are powered, properly connected to
the link, and have the correct node address.
Check the drive-to-drive link wiring.
Check the settings of parameters
57.07
on the master drive.
Check the drive-to-drive link wiring.
Contact your local ABB representative.
Check the connections between the JCU
Control Unit and the power unit.
Contact your local ABB representative.
Informative alarm.
Informative alarm.
Check there are no power factor correction
capacitors or surge absorbers in motor cable.
Check that there is no earth fault in motor or
motor cables:
- measure insulation resistances of motor and
motor cable.
If no earth fault can be detected, contact your
local ABB representative.
Check the settings of the motor configuration
parameters in group
99 START-UP
Check that the drive is sized correctly for the
motor.
57.06
and
DATA.