Siemens SIMATIC MV500 Operating Manual page 113

Optical identification
Hide thumbs Also See for SIMATIC MV500:
Table of Contents

Advertisement

Parameter
Possible values
Result
None
CM
DI/DO
PROFINET IO
SIMATIC MV500
Operating Manual, 05/2019, C79000-G8976-C495-02
Default
Description
DI/DO
Specify the interface over which the result bits READ,
MATCH, and N_OK are output.
None: The result bits READ, MATCH and N_OK are
not output.
CM: Result bits are output over the CM interface.
Note
In order to obtain a result, you must set the result bits
in the program format text (%b) for the "CM" function.
Simply selecting "CM" at this point does not provide a
result.
DI/DO: Result bits are output over the DI/DO inter-
face.
PROFINET IO: Result bits are output over the
PROFINET IO interface.
Note
In order to obtain a result, set the result bits in the
program format text (%b) in "PROFINET IO (Ident
profile)" IP mode. Simply selecting "PROFINET IO" at
this point does not provide a result
Settings
6.1 Communication
113