Settings
6.1 Communication
Relationships and dependencies of the parameters
Table 6- 11
Parameter
Trigger, text
Text, control
Trigger, source
Trigger source,
text, result,
control
Permitted combinations for text and controller settings
Table 6- 12
Permitted combinations for text and controller settings
String "None"
Text "PROFINET IO"
(FB79)
String "PROFINET IO"
(Ident profile)
Text "CM"
Text "TCP"
Text "RS232"
116
Relationships and dependencies of the parameters
Dependency
Source
•
Connections
•
Options > Extras
•
Text
•
Ethernet > IP mode
•
Control
Control
DI/DO
PROFINET IO
(FB79)
☑
☑
☐
☑
☐
☐
☐
☐
☑
☑
☑
☑
Description
The Trigger text input box is only available
•
when the trigger source is selected as
"RS232" or "TCP".
For permitted combinations, refer to the
•
table below.
If "CM" is selected as the trigger source,
•
"CM" must also be selected for the text.
If the IP mode is "PROFINET IO", "CM"
•
cannot be selected as trigger source, text,
result and control.
Control
Control
PROFINET IO
CM
(Ident profile)
☐
☐
☐
☐
☑
☐
☐
☑
☐
☐
☐
☐
Operating Manual, 05/2019, C79000-G8976-C495-02
Control
Control
TCP
RS232
☑
☑
☐
☐
☐
☐
☐
☐
☑
☑
☑
☑
SIMATIC MV500