Commissioning
2.7 First commissioning, vector control mode in the chassis format
What to do?
3.10
Summary
Note
The reference parameters and limit values in the STARTER can be protected from being automatically overwritten by
p0340 = 1. In the STARTER, you will find this under Drive -> Configuration-> Reference parameters / blocked list tab.
4.
Enable signals and
BICO interconnections
4.1
Active Line Module
4.2
Enable Motor Module
102
How to do it?
The drive data can be copied to the clipboard for
plant documentation purposes and then added to a
text program, for example.
The enable signals for the infeed and the two drives
must be realized via the digital inputs on the Control
Unit.
Enable signals for the Active Line Module
p0840 = 722.4 ON/OFF1
p0844 = 722.5 OFF2
p0852 = 722.6 Enable operation
Enable signals for the Motor Module (drive_1)
p0840 = 722.0 ON/OFF1
p0844 = 722.1 1. OFF2
p0845 = 1 2. OFF2
p0848 = 722.2 1. OFF3
p0849 = 1 2. OFF3
p0852 = 722.3 Enable operation
p0864 = 863.0 Infeed operation
Note:
If an Active Line Module is
installed, the same signal source
must not be used to enable both
the infeed and the drive.
See function diagram [8920]
See function diagram [2501]
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1