3.5 Fault and alarm messages
3.5.3

Configuring messages

The properties of the faults and alarms in the drive system are permanently defined.
The following can be configured for some of the messages within a permanently defined
framework for the drive system:
Change message type (example)
Select message
p2118[5] = 1001
Change fault reaction (example)
Select message
p2100[3] = 1002
Change acknowledgement (example)
Select message
p2126[4] = 1003
19 message types per drive object can be changed.
Note
If BICO interconnections exist between drive objects, all interconnected objects must be
configured.
 Example:
230
The TM31 has BICO interconnections with drives 1 and 2, and F35207 is to be
reconfigured as an alarm.
– p2118[n] = 35207 and p2119[n] = 2
– This must be set for TM31 and drives 1/2.
Set message type
p2119[5]
= 1: Fault (F)
= 2: Alarm (A)
= 3: No message (N)
Set fault response
p2101[3]
= 0: None
= 1: OFF1
= 2: OFF2
= 3: OFF3
= 4: STOP1 (available soon)
= 5: STOP2
= 6: IASC/DC brake
Internal armature short-circuit braking or
DC brake
= 7: ENCODER (p0491)
Set acknowledgement
p2127[4]
= 1: POWER ON
= 2: IMMEDIATELY
= 3: PULSE INHIBIT
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1