Diagnostics
3.1 Diagnostics via LEDs
3.1.1.10

Control Unit 310-2PN in operation

Table 3- 14
Description of the LEDs during operation of the CU310-2 PN
LED
Color
RDY
-
(READY)
Green
Red
Red / green Flashing light
Orange
Green /
orange
or
red /
orange
COM
-
Green
Red
MOD
-
OUT > 5 V
-
Orange
1) Make sure that the connected encoder is designed for a 24 V supply. Connecting a 5 V encoder to a 24 V supply can
result in destruction of the encoder electronics.
170
State
Description / cause
Off
Electronic power supply is missing or outside
permissible tolerance range.
Continuous light
The unit is ready for operation.
Cyclic DRIVE-CLiQ communication is in
progress.
Flashing light 0.5
Commissioning / reset
Hz
Flashing light 2 Hz
Writing to the memory card.
Flashing light
General errors
2 Hz
The control unit is ready for operation, but there
0.5 Hz
are no software licenses.
Flashing light
The firmware of the DRIVE-CLiQ components is
0.5 Hz
being updated.
Flashing light
DRIVE-CLiQ component firmware update
2 Hz
completed. Waiting for POWER ON of the
corresponding components.
Flashing light
Detection of the component via LED is activated
2 Hz
(p0124[0]).
Note:
Both options depend on the LED state when
activating via p0124[0] = 1.
Off
Cyclic communication is not (yet) running.
Note: The PROFIdrive is ready for
communication when the Control Unit is ready
for operation (see LED: RDY).
Continuous light
Cyclic communication is taking place.
Flashing light
Cyclic communication is not fully established yet.
0.5 Hz
Possible causes:
- The controller is not transmitting any setpoints.
- In isochronous mode, the controller is not
sending a GC (Global Control) or is sending a
defective GC.
Flashing light
The PROFIBUS master is sending a faulty
0.5 Hz
parameter assignment or the configuration file is
corrupted.
Flashing light
Cyclic bus communication has been interrupted
2 Hz
or could not be established.
Off
-
Off
-
Continuous light
The voltage of the electronic power supply for
the measuring system is 24 V.
1)
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
Remedy
Check the power
supply
-
-
-
Check parameter
assignment /
configuration
Install the missing
licenses.
-
Switch on the
component.
-
-
-
-
Modify the configu-
ration between master
/controller and CU
Rectify the bus
communication fault.
-
-