2.3.2

Important functions via BOP20

Description
Using the BOP20, the following functions can be executed via parameters that support you
when handling projects:
● Restoring the factory settings
● Copy RAM to ROM
● Identification via LED
● Acknowledging faults
Restoring the factory settings
The factory setting of the complete device can be established in the drive object CU.
● p0009 = 30
● p0976 = 1
Copy RAM to ROM
You can initiate the saving of all parameters to the non-volatile memory (memory card) in the
drive object CU:
● Press the P key for 3 seconds,
● p0009 = 0
● p0977 = 1
Identification via LED
The main component of a drive object (e.g. Motor Module) can be identified using the index
of p0124. The "Ready" LED on the component starts to flash. The index matches the index
in p0107. The drive object type can be identified via this parameter.
On the drive objects, the components can also be identified via the following parameters:
● p0124 Power unit detection via LED
● p0144 Voltage Sensing Module detection via LED
● p0144 Sensor Module detection via LED
Acknowledging faults
To acknowledge all the faults that have been rectified, press the Fn key.
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
or
NOTICE
This parameter is not accepted if an identification run (e.g. motor data identification) has
been selected on a drive.
Commissioning
2.3 Basic Operator Panel 20 (BOP20)
77