Commissioning
2.2 STARTER commissioning tool
Assigning the IP address and the name
Note
ST (Structured Text) conventions must be satisfied for the name assignment of IO devices in
PROFINET (SINAMICS components). The names must be unique within PROFINET.
The characters "-" and "." are not permitted in the name of an IO device.
Assignment with STARTER, "Accessible nodes" function
Use the STARTER to assign an IP address and a name to the PROFINET interface (e.g.
CBE20).
● Connect the programming device via Ethernet cable to the Control Unit.
● Switch on the Control Unit.
● Open STARTER.
● A search is performed for available nodes in PROFINET via Project -> Accessible nodes
● The Control Unit as SINAMICS drive object with CBE20 is detected as node with IP
● Mark the bus node entry and select the displayed menu item "Edit Ethernet node" with
● In the following "Edit Ethernet node" screen, enter the device name for the PROFINET
● The "Update (F5)" button displays the IP address and name in the entry for the bus node.
● If the PROFINET interface is displayed as bus node, mark the entry and click the
● The SINAMICS drive with CBE20 is displayed as drive object in the project tree.
● Further configurations can be performed for the drive object.
● Click "Connect to target system" and load the project to the Control Unit's memory card
Note
The IP address and device name for the Control Unit are stored on the memory card
(non-volatile).
64
or the "Accessible nodes" button.
address 0.0.0.0 and is displayed without name.
the right mouse button.
interface and click the "Assign name" button. Enter the IP address (e.g. 192.168.0.2) in
the IP configuration and specify the subnet screen (e.g. 255.255.255.0). Then click the
"Assign IP configuration" button. Close the screen.
If not, close the "Accessible nodes" screen and perform another search for accessible
nodes.
"Accept" button.
with Target system -> Load -> To target device.