CUA32
The parameterization of the temperature evaluation via terminal X210 or sub D socket X220
is performed using two temperature channels.
p0600 = 11: Temperature sensor via Motor Module
For the SINAMICS S120 AC Drive (AC/AC) and if Control Unit Adapter CUA31/CUA32 is
used, the temperature sensor connection is on the adapter (X210).
TM31
With Terminal Module TM31, the sensor type used is set via p4100 and the temperature
signal interconnected via r4105.
SME20
The evaluation of KTY or PTC temperature sensors can be parameterized using the
STARTER screen (\Signals and monitoring \ Motor temperature):
● Temperature sensor selection (≙ p0600[0..n]): Selection of the source to which the SME
● Temperature sensor type (≙ p0601[0..n]): Sets the sensor type for motor temperature
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
module is assigned (temperature sensor via encoder (1, 2 or 3), temperature sensor via
BICO interconnections or temperature sensor via Motor Module)
monitoring.
Figure 2-43
Selection of temperature sensor for SME20 modules
2.16 Temperature sensors for SINAMICS components
Commissioning